D ew p o i n t   p ro b e s  RO D P 6 0  a n d   RO D  P 10 0

Measurement of relative humidity using Rotronic capacitive Hygromer® sensors allows software based calculation of the dew or frost
(Dp/Fp) point temperature. However, below -30°C Dp/Fp specific sensors are recommended.
ROTRONIC offers dew/frost point sensors that are compatible with the HygroFlex transmitter range, and that can also be used as
autonomous 2-wire loop powered transmitters. The sensors used in these products are aluminium oxide based, and are pre-calibrated
over the specific measurement ranges.
 

RODP60 / RODP 100
Features
Dew point measurement to -100 °C (Dp/Fp)
2-wire loop powered
HART digital output signal
Aluminium oxide sensor
High grade stainless steel enclosure
Measurements in pressurised or atmospheric environments
Various connection threads are available

Order code:
RODP60 -60...30 °C (Dp/Fp)
RODP100 -100...20 °C (Dp/Fp)


 

 
Specifications RODP60                                                     RODP100
Sensor Aluminium oxide sensor
Voltage supply 5...28 VDC, 4...20 mA 2-wire loop powered
Dew point range -60...30 °C (Dp/Fp)                      -100...20 °C (Dp/Fp)
Operating range (sensor) -10...70 °C
Operating range (transmitter) -30...85 °C
Accuracy ±2 °C (Dp/Fp)
Repeatability ±0.2 °C
Resolution (input) 0.1 °C (Dp/Fp)
Output signals 4...20 mA or digital HART protocol selectable
Electrical connection 4-pin standard industrial connector, 9.4 mm, IP65
Threading M14 x 1.25 and 3⁄4”-16 UNF-2A, others on request
Enclosure High grade stainless steel enclosure
Dimensions and weight ~32 x 136 mm, 230 g
Approvals (pending)         FM IS Classl,ll,lll, Division 1, Groups A,B,C,D,E,F,G T6 at 40 °C ambient
  T4 at 85 °C ambient
  Class1 Zone 0, AEx ia llC T6 (-20 ≤ Ta ≤ 40 °C);T4 (-20≤ Ta ≤ 85 °C)
  NI Class 1, Division 2, Groups A,B,C & D;
  Suitable for Class ll, Division 2, Groups E,F & G and Class lll, Division 2
                                      NEMKO Ll1 GD ATEX EEx ia llC T6 EEx nA llC T6
Please contact ROTRONIC when you need an EX-rated probe.